A.8 Parameters of the SM 331; AI 8 x 16 bits
Parameters
Table A-23contains all the parameters which you can set for the isolated analog
input module SM 331; AI 8 x bits. This comparison indicates which methods you
can use for the configuration of the individual parameters:
SFC 55 “WR_PARM”
STEP 7 programming device
The parameters that you have set with STEP 7 can also be transferred to the
module by means of SFC 56 or SFC 57.
Table A-23 Parameters for the isolated analog input module SM 331; AI 8 x 16 bits
Parameter
Data Record
Configurable with...
Parameter
Data Record
No.
... SFC 55 ...programming device
Diagnostics: Group diagnostics
0
No Yes
Diagnostics: With wire-break
check
0
No Yes
Limit value interrupt enable
1
Yes Yes
Diagnostics interrupt enable
1
Yes Yes
Cycle end interrupt enable Yes Yes
Module mode Yes Yes
Interference Suppression Yes Yes
Measuring Method Yes Yes
Measuring Range
128
Yes Yes
Smoothing
128
Yes Yes
Upper limit value Yes Yes
Lower limit value Yes Yes
Note
If you want to enable the diagnostic interrupt in the user program in data record 1,
you must enable the diagnosis in data record 0 beforehand using STEP 7.