EasyManua.ls Logo

Siemens Simatic S7-300 - Sinusoidal Interference

Siemens Simatic S7-300
574 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
General Technical Specifications
1-7
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Additional measures
If you want to connect an S7-300 system to the public network, you must ensure
Limit Value Class B in accordance with EN 55022.
Sinusoidal interference
The table below shows the EMC behavior of the S7-300 modules with regard to
sinusoidal disturbance variables.
Table 1-3 Sinusoidal Interference
Sinusoidal Interference
Test values Satisfies
degree of
severity
HF irradiation (electromagnetic fields)
according to IEC 61000-4-3
according to IEC 61000-4-3
10 V/m with 80% amplitude modulation of 1 kHz
over the range from 80 MHz to 1000 MHz
10 V/m with 50% pulse modulation at 900 MHz
3
HF conductance on cables and cable
shields according to IEC 61000-4-6
Test voltage 10 V with 80% amplitude modula-
tion of 1 kHz over the range from 9 MHz to
80 MHz
3
Emission of radio interference
Interference emission of electromagnetic fields in accordance with EN 55011: Limit
value class A, Group 1.
From 30 to 230 MHz < 40 dB (V/m)Q
From 230 to 1000 MHz < 47 dB (V/m)Q
Measured at a distance of 10 m (98.4 ft.)
Interference emission via the mains AC power supply in accordance with
EN 55011: Limit value class A, Group 1.
From 0.15 to 0.5 MHz < 79 dB (V)Q
< 66 dB (V)M
From 0.5 to 5 MHz < 73 dB (V)Q
< 60 dB (V)M
From 5 to 30 MHz < 73 dB (V)Q
< 60 dB (V)M

Table of Contents