Analog Modules
4-43
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
4.7.2 Parameters of the Analog Output Modules
The analog output modules use a subset of the parameters and ranges of values
listed in the table below, depending on the functionality. Refer to the section on the
module concerned, starting from Section 4.28, for the subset “mastered” by the
specific analog modules.
The default settings apply if you have not performed parameter assignment in
STEP 7.
Table 4-42 Parameters of the Analog Output Modules
Parameter
Value Range Default
Settings
Para-
meter Type
Scope
Enable
Diagnostic
interrupt
Yes/no No Dynamic Module
Diagnostics
Group diagnostics Yes/no No Static Channel
Output
Output type Deactivated
Voltage
Current
U
Dynamic Channel
Output range For the settable measuring ranges of the
output channels, please refer to the
individual module description.
"10 V
Response with
CPU-STOP
ASS Outputs de-energized
LWH Hold last value
EWS Apply substitute value
ASS
Dynamic Channel