A-38
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Setting substitute values
Note
For output ranges 4 to 20 mA and 1 to 5 V you must set the substitute value
E500
H
so that the output remains de-energized (refer to Tables 4-35 and 4-37 on
pages 4-26 and 4-27).
The representation of the substitute values corresponds to the analog value
representation. You should observe the relevant range limits when setting the
substitute values.
Output methods and output ranges
The table below contains all the output methods and output ranges of the analog
output modules and their codes. You must enter these codes in bytes 2 to 5 of
data record 1 (refer to FigureA-17).
Table A-29 Codes for the Output Ranges of the Analog Output Modules
Output type
Code Output Range Code
Deactivated 2#0000 Deactivated 2#0000
Voltage 2#0001 1 to 5 V
0 to 10 V
" 10 V
2#0111
2#1000
2#1001
Current 2#0010 0 to 20 mA
4 to 20 mA
" 20 mA
2#0010
2#0011
2#0100