Analog Modules
4-81
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
4.18.1 Commissioning the SM 331; AI 8 x 16 bits
You set the mode of operation of the SM 331; AI 8 x 16 bits STEP 7.
Parameter
You will find a description of the general procedure for assigning parameters to
analog modules in Section 4.7.
An overview of the parameters that you can set and their default settings are
shown in the table below.
Table 4-50 Parameters of the SM 331; AI 8 x 16 bits
Parameter
Value Range Default
Settings
Para-
meter
Type
Scope
Enable
Diagnostic interrupt
Hardware interrupt
upon limit violation
Yes/no
Yes/no
No
No
Dynamic Module
Trigger for hardware
interrupt
Upper limit value
Lower limit value
Constraint possible due to measuring
range.
32511 to –32512
–32512 to 32511
Dynamic
Channel
Diagnostics
Group diagnostics
With wire-break
check
Yes/no
Yes/no
No
No
Static
Channel
group
Measurement
Measuring Method Deactivated
U Voltage
4DMU Current (4-wire transmitter)
U
Channel
Measuring Range Refer to Section 4.18.2 for the
measuring ranges of the input
channels that you can set.
"10 V
Dynamic
Channel
group
Interference
Suppression
400 Hz; 60 Hz; 50 Hz; 10 Hz 50 Hz