Digital Modules
3-75
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Technical specifications of the SM 322; DO 8 x 24 VDC/0.5 A
Dimensions and Weight
Dimensions W x H x D
(in millimeters)
40 x 125 x 117
Weight Approx. 210 g
Data for Specific Module
Supports clocked
operation
No
Number of outputs 8
Length of cable
Unshielded
Shielded
max. 600 m
max. 1000 m
Voltages, Currents, Potentials
Rated load voltage L+ 24 VDC
Total current of the outputs (per
group) without series diode
Horizontal configuration
Up to 40 C
Up to 60 C
max. 4 A
max. 3 A
Vertical configuration
Up to 40 C max. 4 A
Total current of the outputs (per
group) with series diode
Horizontal configuration
Up to 40 C
Up to 60 C
max. 3 A
max. 2 A
Vertical configuration
Up to 40 C max. 3 A
Isolation
Between channels and
backplane bus
Yes
Permitted potential difference
Between the different
circuits
75 VDC / 60 VAC
Insulation tested with 500 VDC
Current consumption
From the backplane bus
From load voltage L+
(without load)
max. 70 mA
max. 90 mA
Power dissipation of the module typ. 5 W
Status, Interrupts, Diagnostics
Status display Green LED per channel
Interrupts
Diagnostic interrupt Parameters can be
assigned
Diagnostic functions
Group error display
Channel error display (F)
Diagnostics information
readable
Parameters can be
assigned
Red LED (SF)
Red LED (F) per
channel
Possible
Data for Selecting an Actuator
Output voltage
At signal “1”
Without series diode
With series diode
min. L + (–0.8 V)
min. L + (–1.6 V)
Output current
At signal “1”
Rated value
Permitted range
0.5 A
10 mA to 0.6 A
1)
At signal “0”
(leakage current)
max. 0.5 mA
Output delay (for resistive load)
At “0” to “1”
At “1” to “0”
max. 180 s
max. 245 s
Load resistor range 48 to 3 k
Lamp load max. 5 W
Parallel connection of
2 outputs
For redundant
actuation of a load
Output with series
diode only, must have
the same reference
potential
To increase performance Not possible
Triggering a digital input Possible
1 binary input
according to
IEC 61131, Type 2;
Type 1 with disabled
open-circuit monitoring
Switch rate
For resistive load
Inductive load according to
IEC 947-5-1, 13 DC
For lamp load
max. 100 Hz
max. 2 Hz
max. 10 Hz
Limit (internal) of the inductive
circuit interruption voltage up
typ. L + (–45 V)
Short-circuit protection of the
output
Yes, electronic
Threshold on typ. 0.75 A to 1.5 A
1)
5 mA to 0.6 A with disabled open-circuit
monitoring