Digital Modules
3-89
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Technical specifications of the SM 322; DO 8 x 120/230 VAC/2 A ISOL
Dimensions and Weight
Dimensions W x H x D 40 x 125 x 117
Weight Approx. 275 g
Data for Specific Module
Supports clocked
operation
No
Number of outputs 8
Length of cable
Unshielded
Shielded
max. 600 m
max. 1000 m
Voltages, Currents, Potentials
Rated load voltage L1 120/230 VAC
Total current of the outputs
(module)
Horizontal configuration
Up to 40 °C
Up to 60 °C
max. 8 A
max. 4 A
Vertical configuration
Up to 40 °C
max. 4 A
Isolation
Between channels and
backplane bus
Yes
Between channels
In groups of
Yes
1
Permitted potential difference
Between M
internal
and the
outputs
230 VAC
Between outputs 500 VAC
Insulation tested with
Between M
internal
and the
outputs
1500 VAC
Between the outputs of the
different groups
2000 VAC
Current consumption
From the backplane bus
From load voltage L1
(without load)
max. 100 mA
max. 2 mA
Power dissipation of the module typ. 8.6 W
Status, Interrupts, Diagnostics
Status display Green LED per channel
Interrupts
Diagnostic interrupt Parameters can be
assigned
Diagnostic functions
Group error display Red LED (SF)
Data for Selecting an Actuator
Output voltage
At signal “1” min. L1 (–8.5 V)
Output current
At signal “1”
Rated value
Permitted range for 0 °C to
40 °C
2 A
10 mA to 2 A
Permitted range for
40 °C to 60 °C
10 mA to 1 A
Permitted surge current
(per group)
max. 20 A
(with 2 half-waves)
For “0” signal
(leakage current)
max. 2 mA
Zero cross inhibit voltage max. 60 V
Size of the motor starter max. size 5 to NEMA
Lamp load max. 50 W
Connecting two outputs in
parallel
For redundant triggering of
a load
Possible
To increase performance Not possible
Triggering a digital input Possible
Switch rate
For resistive load max. 10 Hz
Inductive loads, according
to IEC 947-5-1, AC 15
max. 0.5 Hz
For lamp load max. 1 Hz
Short-circuit protection of output Yes,
3.15 A /
250 V fuse, fast-acting

Table of Contents