Digital Modules
3-99
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Data for Selecting an Actuator, continued
Lamp load
1)
max. 50 W
Power No. of
switching
cyc. (typ.)
Lamp load (230 VAC)
2)
1000 W
1500 W
25000
10000
Energy-saving
lamps/fluorescent lamps with
electronic ballast
2)
10 58W 25000
Fluorescent lamps,
conventionally compensated
2)
1 58W 25000
Fluorescent lamps,
non-compensated
2)
10 58W 25000
Connecting two outputs in parallel
For redundant triggering of
a load
Possible (only outputs
of the same group)
To increase performance Not possible
Triggering a digital input Possible
Switch rate
Mechanical max. 10 Hz
For resistive load max. 2 Hz
Inductive loads according
to IEC 947-5-1, DC 13/15
AC
max. 0.5 Hz
For lamp load max. 2 Hz
1)
Product status 1
2)
Product status 2 or later