Analog Modules
4-171
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Technical specifications of the SM 332; AO 4 x 16 bit
Dimensions and Weight
Dimensions W x H x D
(in millimeters)
40 x 125 x 117
Weight Approx. 220 g
Data for Specific Module
Supports clocked
operation
Yes
Changing parameters during
the RUN
possible
Yes
Behavior of the non
parameterized outputs
outputs the last valid
output value before the
parameterization
Number of outputs 4
Length of cable
Shielded max. 200 m
Voltages, Currents, and Potentials
Rated load voltage L+
Reverse polarity protection
24 VDC
Yes
Isolation
Between channels and
backplane bus
Yes
Between channels and
power supply of the
electronics
Yes
Between the channels Yes
Permitted potential difference
Between the outputs (ECM) 200 VDC / 120 VAC
Between M
ANA
and
M
internal
(U
ISO
)
200 VDC / 120 VAC
Insulation tested with 500 VDC
Current consumption
From the backplane bus max. 100 mA
From the load voltage L+
(no load)
max. 240 mA
Power dissipation of the module typ. 3 W
Analog value generation
Resolution
(incl. sign)
"10 V 16 bits
0 to 10 V 15 bits
1 to 5 V 14 bits
" 20 mA 15 bits
0 to 20 mAV 14 bits
4 to 20 mA 14 bits
Conversion time (per channel)
in standard operation
in clocked operation
max. 0.8 ms
1.6 ms
Basic response time of module
(independent of number of
released channels)
in standard operation
in clocked operation
3.2 ms
2.4 ms
Settling time
For resistive load
For capacitive load
For inductive load
0.2 ms
3.3 ms
0.5 ms (1 mH)
3.3 ms (10 mH)
Suppression of interference, Limits of Error
Crosstalk between
outputs
> 100 dB
Operational limit (in the entire temperature range, with
reference to the output range)
Voltage outputs "0.12%
Current outputs "0.18%
Basic error (operational limit at 25° C, referred to output
range)
Voltage outputs
" 10 V
0 to 10 V
1 to 5 V
"0.02%
"0.02%
"0.04%
Current outputs
" 20 mA
0 to 20 mA;
4 to 20 mA
"0.02%
"0.02%
"0.04%
Temperature error (with
reference to the output range)
Voltage outputs
Current outputs
"0.0025% / K
"0.004% / K
Linearity error (with reference to
the output range)
"0.004%
Repeat accuracy (in the steady
state at 25° C, referred to the
output range)
"0.002 %
Output ripple; band width 0 to
50 kHz (with reference to the
output range)
"0.05%