Analog Modules
4-178
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Technical specifications of the SM 332; AO 4 x 12 bits
Dimensions and Weight
Dimensions W x H x D
(in millimeters)
40 x 125 x 117
Weight Approx. 220 g
Data for Specific Module
Supports clocked
operation
No
Number of outputs 4
Length of cable
Shielded max. 200 m
Voltages, Currents, Potentials
Rated load voltage L +
Reverse polarity protection
24 VDC
Yes
Isolation
Between channels and
backplane bus
Yes
Between channels and
power supply of the
electronics
Yes
Between the channels No
Between channels and load
voltage L+
Yes
Permitted potential difference
Between S– and M
ANA
(U
CM
)
3 VDC
Between M
ANA
and
M
internal
(U
ISO
)
75 VDC / 60 VAC
Insulation tested with 500 VDC
Current consumption
From the backplane bus max. 60 mA
From the load voltage L+
(no load)
max. 240 mA
Power dissipation of the module typ. 3 W
Analog value generation
Resolution including sign
" 10 V; " 20 mA;
4 to 20 mA; 1 to 5 V
11 bits + sign
0 to 10 V; 0 to 20 mA 12 bits
Conversion time (per channel) max. 0.8 ms
Settling time
For resistive load
For capacitive load
For inductive load
0.2 ms
3.3 ms
0.5 ms (1 mH)
3.3 ms (10 mH)
Suppression of interference, Limits of Error
Crosstalk between the outputs > 40 dB
Operational limit (in the entire temperature range, with
reference to the output range)
Voltage outputs
Current outputs
" 0.5 %
" 0.6 %
Basic error (operational limit at 25° C, referred to output
range)
Voltage outputs
Current outputs
" 0.4 %
" 0.5 %
Temperature error (with
reference to the output range)
" 0.002 %/K
Linearity error (with reference to
the output range)
" 0.05 %
Repeatability (in steady state at
25 C, referred to output range)
" 0.05 %
Output ripple; range 0 to 50 kHz
(referred to output range)
" 0.05 %
Status, interrupts, diagnostics
Interrupts
Diagnostic interrupt Parameters can be
assigned
Diagnostic functions Programmable
Group error display Red LED (SF)
Diagnostic information
readable
Possible
Substitute value can be applied Yes, programmable