EasyManuals Logo

Siemens SIMATIC User Manual

Siemens SIMATIC
648 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #179 background imageLoading...
Page #179 background image
Digital modules
3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0)
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
179
3.29.2 SM 322; DO 8 x DC 24 V/0.5 A - Diagnostics
Diagnostics messages of SM 322; DO 8 x DC 24 V/0.5 A
The table provides an overview of the diagnostic messages of
SM 322; DO 8 x DC 24 V/0.5 A
Table 3- 29 Diagnostics messages of SM 322; DO 8 x DC 24 V/0.5 A
Diagnostics message
LED
Scope of diagnostics
programmable
Wire-break*
SF
Channel
yes
Load voltage missing SF Channel yes
Short-circuit to M
SF
Channel
yes
Short-circuit to L+ SF Channel yes
External auxiliary voltage missing
SF
Module
no
Internal auxiliary voltage missing
SF
Module
no
Fuse blown
SF
Module
no
Watchdog time-out
SF
Module
no
EPROM fault
SF
Module
no
RAM fault
SF
Module
no
*
The module detects a wire-break at a current < 1 mA.
If configured accordingly, the
SF LED and corresponding channel error LED light up when a wire-break is detected.
Note
Prerequisite for the detection of errors indicated by programmab
le diagnostic messages is
an appropriate configuration of the digital module in
STEP 7
.

Table of Contents

Other manuals for Siemens SIMATIC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC and is the answer not in the manual?

Siemens SIMATIC Specifications

General IconGeneral
Product type designationSIMATIC
CPUVaries by model
MemoryVaries by model
Input/OutputVaries by model
CommunicationVaries by model
Programming LanguageSTEP 7
Operating Temperature0°C to 60°C (varies by model)
Protection ClassIP20
CategoryProgrammable Logic Controller (PLC)

Related product manuals