Analog modules
6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0)
S7-300 Module data
324 Manual, 06/2017, A5E00105505-AJ
6.4.2 Programmable parameters
Introduction
For information on programming analog modules, refer to the chapter Programming analog
modules (Page 294).
Parameter
Table 6- 11 Overview of parameters of SM 331; AI 8 x 16 Bit
Parameters
Range of values
Defaults
Parameter type
Scope
Enable
•
Process interrupt when limit value
is exceeded
• Process interrupt at end of cycle
• Diagnostics interrupt
yes/no
yes/no
yes/no
no
no
no
dynamic
dynamic
dynamic
Module
Process interrupt trigger
• High limit
• Low limit
32511 to -32512
-32512 to 32511
-
-
dynamic
dynamic
Channel
Channel
Diagnostics
• Group diagnostics
• Line continuity check
yes/no
yes/no
no
no
static
Channel
Channel
Measurement
• Module operating mode
• Noise suppression
• 8 channels
• 4 channels
50 Hz
60 Hz
400 Hz
50/60/400 Hz
yes
no
50/60/400 Hz
dynamic
Module
Channel group
• Smoothing • none
• weak
• medium
• strong
none
dynamic
Channel group
• Measurement type • Measuring range:
dynamic Channel group
disabled
Voltage
• ± 5 V
• 1 V to 5 V
• ± 10 V
± 10 V
Current (4-wire transducer)
• 0 mA to 20 mA
• 4 mA to 20 mA
• ± 20 mA
4 mA to 20 mA
See also
Diagnostics messages of analog input modules (Page 296)
Programming analog modules (Page 294)