Digital modules
3.34 Relay output module SM 322; DO 8 x Rel. AC 230 V; (6ES7322-1HF01-0AA0)
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
207
Fluorescent lamps, conventionally compensated
2)
Fluorescent lamps, non-compensated
2)
10 x 58 W 25000
Wiring two outputs in parallel
• for redundant load control
supported (only outputs of the same group)
• for performance increase
not supported
Control of a digital input supported
Switching frequency
• Mechanical
max. 10 Hz
• with resistive load
max. 2 Hz
• with inductive load to IEC 947-5-1, DC13/AC15
max. 0.5 Hz
• with lamp load
max. 2 Hz
using a 20-pin front connector
1) Product version 1