Principles of analog modules
5.1 Representation of the values for analog input channels
S7-300 Module data
272 Manual, 06/2017, A5E00105505-AJ
Representation of the analog values for Cu 10, 50, 100, 500 GOST standard (0.00428) resistance
thermometers
Table 5- 21 Representation of the analog values for Cu 10, 50, 100, 500 GOST standard (0.00428) resistance thermome-
ters
Cu x0 stan-
dard in °C
(1 digit =
0.01 °C)
Cu x0 stan-
dard in °F
(1 digit =
0.01 °F)
240.0
:
200.1
2400
:
2001
0960
H
:
07D1
H
464.0
:
392.1
4640
:
3921
1220
H
:
0F51
H
Overshoot range
200.0
:
2000
:
07D0
H
:
H
392.0
:
3920
:
0F50
H
:
H
Rated range
-200.1
:
-2001
:
F82F
H
:
-328.1
:
-3281
:
F32F
H
:
Undershoot range
H
H
Representation of analog values for KTY83/110 silicon temperature sensors
Table 5- 22 Representation of analog values for KTY83/110 silicon temperature sensors
KTY83/110 in
°C
(1 digit = 0.1
°C)
KTY83/110
in °F
(1 digit =
0.1 °F)
KTY83/110
in °K
(1 digit =
0.1 °K)
206.3
:
2063
:
080F
H
:
H
403.3
:
4033
:
0FC1
H
:
H
479.5
:
4795
:
12BB
H
:
H
Overshoot
range
175
:
1750
:
06D6
H
:
347
:
3470
:
0D8E
H
:
448.2
:
4482
:
1182
H
:
Rated range
-55.1
:
-551
:
FDD9
H
:
H
-67.1
:
-671
:
FD61
H
:
H
218.1
:
2181
:
0885
H
:
H
Undershoot
range
H
H
H