Analog modules
6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0)
S7-300 Module data
370 Manual, 06/2017, A5E00105505-AJ
Wiring: 2-, 3- and 4-wire connection of resistance transducers or thermoresistors
3-wire connection, no compensation for line resistors
2-wire connection, no compensation for line resistors
Figure 6-19 Wiring and block diagram
Measuring range module settings
Measuring range module setting
300 Ω
RTD-4L: Thermal resistance
(linear, 4-wire connection) (temperature
measurement)
Ni 100 Klima
Pt 100 Standard
Note
"Resistance measurement" is only available at one channel per group. The "2nd" channel of
the group is used accordingly
for current measuring mode (I
C
).
The "1st" returns the measured value. The "2nd" channel of the group is assigned the default
overflow value "7FFF
H
."