Analog modules
6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0)
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
385
Technical specifications
Temperature error (in relation to input range)
Resistance thermometer
Resistor
± 0.015 °C/K
± 0.005 %/K
Linearity error (referenced to input range)
Resistance thermometer
Resistor
± 0.2 °C
± 0.02 %
Repeat accuracy (in steady state at 25 °C, referenced to input
range)
Resistance thermometer
Resistor
± 0.2 °C
± 0.01 %
Status, interrupts, diagnostics
Interrupts
Hardware interrupt
Diagnostics interrupt
Configurable (channels 0-7)
Configurable
Diagnostics function
Group error display
Diagnostic information can be read
Configurable
Red LED (group error)
possible
Encoder selection data
Input range (rated values) input resistance
Resistance thermometer
Resistor
Pt 10, Pt 50, Pt 100, Pt 200, Pt 500, Pt 1000,
Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000, LG-Ni
1000, Cu 10, Cu 50, Cu 100 (standard and climatic)
150, 300, 600
Permissible input voltage at voltage input (destruction limit) 35 V DC continuous 75 V DC for max. 1 s (duty
cycle 1 : 20)
Wiring of the signal transmitters
for resistance measurement
with 2-wire connection
with 3-wire connection
with 4-wire connection
with 40-pin front connector
possible
possible***
possible
Characteristic linearization
Resistance thermometer
Technical unit for temperature measurement
Pt 10, Pt 50, Pt 100, Pt 200, Pt 500, Pt 1000,
Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000, LG-Ni
1000, Cu 10, Cu 50, Cu 100 (standard and climatic)
Degrees Celsius / degrees Fahrenheit
* The resistance test for compensation of the line resistances with a 3-wire connection is performed every 5 minutes.
** Wire break monitoring in 4-channel mode (hardware filter) is performed every 3 seconds.
*** The maximum line resistance with 3-wire encoder measurements for the RTD elements PT 10 and Cu 10 is 10 Ω. For
all other RTD elements, the maximum power resistance for 3-wire encoder measurements is 20 Ω.
**** In 4-channel mode, the converted value settles to 100% within 80 ms. The value determined in this process is
switched typically every 3.3 ms (max. 10 ms).

Table of Contents

Other manuals for Siemens SIMATIC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC and is the answer not in the manual?

Siemens SIMATIC Specifications

General IconGeneral
Product type designationSIMATIC
CPUVaries by model
MemoryVaries by model
Input/OutputVaries by model
CommunicationVaries by model
Programming LanguageSTEP 7
Operating Temperature0°C to 60°C (varies by model)
Protection ClassIP20
CategoryProgrammable Logic Controller (PLC)

Related product manuals