6.1.2 Selecting cables
Take the following criteria into account when selecting the connecting cables:
Rated current
Rated voltage
If required, service factor
System-dependent conditions, such as ambient temperature, routing type, cable cross-
section as de󹪝ned by required length of cable, etc.
Con󹪝guration notes
Requirements according to IEC/EN60204‑1
Dimensioning for bundled cable routing, e.g. according to DINVDE0298Part4 or
IEC60364-5-52
6.1.3 Thermal protection
Protect every explosion-protected machine according to EN / IEC 60079-14 Chapter "Rotating
electrical machines".
For machines with type of protection increased safety "eb", select the overcurrent device with
current-dependent delayed trip so that the tripping time, which should be taken from the
characteristic of the switch for the ratio I
A
/ I
N
of the machine to be protected, is not longer
than the safe locked rotor time (t
E
). Take the ratio I
A
/ I
N
as well as the safe locked rotor time
(t
E
) from the rating plate. Set the protective device to the rated current. Use a trip unit
certi󹪝ed according to directive 2014/34/EU or the corresponding national regulations.
For machines with increased safety "eb" type of protection, in the event of a locked rotor the
protective device must disconnect within the safe locked rotor time (t
E
) speci󹪝ed for the
relevant temperature class. Protect electrical machines for heavy duty starting (acceleration
time > 1.7 x t
E
time) according to the speci󹪝cations of the EU-type examination certi󹪝cate
using a function to monitor starting.
Direct monitoring of the winding temperature is permissible as a means of thermal machine
protection, provided that this is certi󹪝ed and speci󹪝ed on the rating plate.
With pole-changing machines, separate, interlocked protective devices are required for each
speed step. Devices with an EU-type examination certi󹪝cate are recommended.
See also
Thermal protection (Page51)
Electrical connection
6.1Connecting the machine
1MB..1/2/3/4 - shaft heights 63 ... 355
Operating Instructions, 11/2023, A5E52779900A 79

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTICS XP 1MB 1 Series and is the answer not in the manual?

Siemens SIMOTICS XP 1MB 1 Series Specifications

General IconGeneral
BrandSiemens
ModelSIMOTICS XP 1MB 1 Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals