You have reset the password for the safety functions.
Parameter Description
p0010 = 95 Drive commissioning parameter filter
Safety Integrated commissioning
p9761 Enter a password (factory setting: 0000 hex)
Permissible passwords lie in the range 1 … FFFF FFFF.
p9762 New password
p9763 Confirm password
p9701 = DC
hex
Confirm data change (factory setting: 0)
Confirm the SI basic parameter change.
p0010 = 0 Drive commissioning parameter filter
0: Ready
p0971 = 1 Save parameter
1: Save the drive object (copy from RAM to ROM)
After the inverter has saved the parameters in a non-volatile fashion, then p0971 = 0.
Commissioning
5.7 Resetting the password for the safety functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD 111

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals