5.9.1 Configuring PROFIsafe via basic functions
Telegram 30 is preset as default in the inverter.
Configuring the PROFIsafe address
You must set the PROFIsafe addresses in the inverter and in the higher-level control system
to the same value.
Figure 5-2 Example: PROFIsafe address 64 hex of the inverter in the STEP 7 hardware configuration
A
Figure 5-3 Configuring the PROFIsafe address with STARTER
The PROFIsafe address of the inverter must be unique in the higher-level control system and
within the network itself.
Parameter Description
p9610 PROFIsafe address (factory setting: 0000 hex)
Commissioning
5.9 Configuring safety functions and PROFIsafe using STARTER
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
116 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals