Special requirements placed on EMC-compliant installation
Use shielded signal cables. Connect the shield at both conductor ends.
In order to connect two or more inverter terminals, use the shortest possible jumpers directly
at the terminals themselves.
Bright and dark test
The inverter filters signal changes using bright and dark tests at the fail-safe digital input using
an adjustable software filter.
4.4.2 Wiring examples according to SIL 2 and PL d
Examples for wiring the fail-safe digital inputs corresponding to PL d according to EN 13849-1
and SIL 2 according to IEC 61508 are provided on the following pages.
In order to reduce the scope of the examples, not all of the SINAMICS inverter types are listed
in each wiring example.
If, in an example, two or more terminals of the inverter are connected together, then you must
connect jumpers that are as short as possible directly at the terminals.
Installing
4.4 Controlling via a fail-safe digital input
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
62 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating