5.12.2.3 Interconnecting the signal for fail-safe acknowledgment
Preconditions
You are online with STARTER or Startdrive.
You have selected the extended functions via onboard terminals.
Procedure with STARTER
To assign the fail-safe acknowledgement signal to a fail-safe digital input, proceed as follows:
1. Press the "Safety inputs/outputs" button.
2. Press the "Configuration" button.
3. Select a free safety-related digital input for the fail-safe acknowledgment signal.
If there are no free fail-safe digital inputs available, you have to acknowledge the safety
function faults using a different method.
Acknowledging using a fail-safe signal (Page 299)
4. Close the screen forms.
You have interconnected fail-safe acknowledge signal with a fail-safe digital input.

Commissioning
5.12 Setting extended functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
162 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals