STOP F
If a safety function is active
1)
, a STOP F initiates a STOP A or STOP B:
Fault F01611 immediately initiates a STOP A.
For message C01711, the inverter response depends on the active safety function:
When STO is active, then the inverter initiates a STOP A.
In all other cases, the inverter initiates a STOP B.
If none of the safety functions are active, then the inverter responds as follows:
Fault F01611 immediately initiates a STOP A.
There is no immediate stop response for message C01711. However, the message is kept.
When selecting a safety function, the inverter responds with a stop as described above.
1)
The SSM function is considered as active safety function if the SSM filter and the SSM
hysteresis have been enabled.
Operation
6.10 Stop responses
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD 295

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals