EasyManua.ls Logo

Siemens SINAMICS G120C - Manual download from the memory card using Startdrive

Siemens SINAMICS G120C
450 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Status
4. Deselect STO
4.1. Deselect STO.
4.2. Check the following:
STO is not active (r9722.0 = 0).
The inverter signals neither faults nor alarms of the safety functions
(r0945[0…7], r2122[0…7]).
You have performed the acceptance test of the STO function.
Appendix
A.2 Examples of acceptance tests
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
386 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD

Table of Contents

Other manuals for Siemens SINAMICS G120C

Related product manuals