Status
3. Select SS1
3.1. Select SS1 while the motor is switched on.
Test each configured activation, e.g. via digital inputs and PROFIsafe.
3.2. In your machine, check the following:
The motor brakes on the OFF3 ramp.
SS1 is active (r9773.6 = 1).
After the p9652 time has expired, the inverter signals: "STO is active"
(r9773.1 = 1).
4. Deselect SS1
4.1. Deselect SS1.
4.2. Check the following:
SS1 is not active (r9773.6 = 0).
The inverter signals neither faults nor alarms of the safety functions
(r0945[0…7], r2122[0…7]).
You have completed the acceptance test of the SS1 function.
Appendix
A.2 Examples of acceptance tests
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
388 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals