Commissioning
8.6 Procedure for configuring PROFIsafe communication
Safety Integrated
Function Manual, 05/2010, A5E03264275A
215
Creating a safety master
1. Create an F-CPU, e.g. CPU 317F-2, and a drive, e.g. SINAMICS S120 with CU320-2, in
accordance with the hardware installed in HW Config.
To do this, start SIMATIC Manager and create a new project.
Figure 8-13 Creating a new project
2. Create a SIMATIC S300 Station under "Insert".
Figure 8-14 Creating a new station
3. The HW Config tool opens by double-clicking on SIMATIC S300(1), and then on
"Hardware".
Figure 8-15 Calling HW Config