EasyManua.ls Logo

Siemens SINAMICS S150 - Page 251

Siemens SINAMICS S150
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Acceptance test and acceptance report
10.2 Acceptance test structure
Safety Integrated
Function Manual, 05/2010, A5E03264275A
251
4. Test of the SI function "Safe Stop 2" (SS2)
Only required when used in Extended Functions
This test is also required if you are not explicitly using SS2 but just one function for
which STOP C occurs as a fault reaction.
Alternatively, you can also carry out the quality test using STOP C yourself, if you use
the table from section "Acceptance test for Safe Stop 2 (Extended Functions)".
Trace recording is required
5. Test of the SI function "Safe Operating Stop" (SOS)
Only required when used in Extended Functions
This test is also required if you are not explicitly using SOS, but just one function for
which STOP C or STOP D occurs as a fault reaction.
Alternatively, you can also perform the quality test using STOP C and STOP D
yourself, if you use the table from section "Acceptance test for Safe Operating Stop
(Extended Functions)".
Trace recording is required
6. Test of the SI function "Safely Limited Speed" (SLS)
Only required when used in Extended Functions
A trace recording is required for each SLS limit
7. Test of the SI function "Safe Speed Monitor" (SSM)
Only required when used in Extended Functions
Trace recording is required
C) Functional testing of forced dormant error detection
Test of the forced dormant error detection of the safety functions on each drive (for each
control mode) and the TM54F (if used).
1. Test of the forced dormant error detection of the safety function on the drive
If you are using Basic Functions, you need to activate and then deactivate STO once
again.
If you are using Extended Functions, you need to carry out a test stop.
2. Test of the forced dormant error detection of the TM54F (if present)
Only if Extended Functions are used
Carry out test stop of the TM54F
D) Functional testing of actual value acquisition

Table of Contents

Other manuals for Siemens SINAMICS S150

Related product manuals