Operation 
  6.7 Control via the operator panel 
Drive converter cabinet units 
Operating Instructions, 07/07, A5E00288214A 
227 
Scalings for vector object 
Table 6-19  Scalings for vector object 
Size  Scaling parameter  Default for quick commissioning 
Reference speed  100 % = p2000  p2000 = Maximum speed (p1082) 
Reference voltage  100 % = p2001  p2001 = 1000 V 
Reference current  100 % = p2002  p2002 = Current limit (p0640) 
Reference torque  100 % = p2003  p2003 = 2 x rated motor torque 
Reference power  100 % = r2004  r2004 = (p2003 x p2000 x π) / 30 
Reference frequency  100% = p2000/60   
Reference modulation depth  100 % = Maximum output voltage without overload  
Reference flux  100 % = Rated motor flux   
Reference temperature  100% = 100°C   
Object A_INF 
Table 6-20  List of signals for the operation screen - object A_INF 
Signal    Parameters  Short name Unit  Scaling (100 %=...) See 
table below 
DC link voltage smoothed   (1) r0026  U_DC  V  p2001 
Input voltage   (2) r0025  U_IN  V  p2001 
Active current   (3) r0030  IACTV  A  p2002 
Line frequency   (4) r0024  FLINE  Hz  p2000 
Active power   (5) r0032  PACTV  kW  r2004 
Actual value of current  (6) r0027  I_IST  A  p2002 
Temperature of power unit   (7) r0037  T_LT  °C  Reference temperature 
Power factor, smoothed   (8) r0032  PACTV  kW  r2004 
Modulation depth, smoothed   (9) r0028  AUSST  %  Reference modulation 
depth 
Reactive current component smoothed   (10) r0029  IREAC  A  p2002 
Scalings for object A_INF 
Table 6-21  Scalings for object A_INF 
Variable  Scaling parameter  Default for quick 
commissioning 
Reference frequency  100 % = p2000  p2000 = p0211 
Reference voltage  100 % = p2001  p2001 = r0206/r0207 
Reference current  100 % = p2002  p2002 = r0207 
Reference power  100 % = r2004   r2004 = r0206 
Reference modulation depth  100 % = Maximum output voltage without overload   
Reference temperature  100% = 100°C