Detailed Description
2.5 Optimization of the control
Velocities, Setpoint/Actual-Value Systems, Closed-Loop Control (G2)
Function Manual, 08/2005 Edition, 6FC5397-0BP10-0BA0
2-63
New setting rule for MD32810 and MD32800
If the new filter is active, the setting rule for machine data:
MD32810 $MA_EQUIV_SPEEDCTRL_TIME
and
MD32800 $MA_EQUIV_CURRCTRL_TIME are modified.
This means that, if the old balancing filter had previously been active and is to be changed to
the new filter, the following actions must be considered:
Setting the equivalent time constant with speed feedforward control
If the previous setting was MD32620 $MA_FFW_MODE = 1:
1. Set MD32620 $MA_FFW_MODE = 3.
2. Set MD32610 $MA_VELO_FFW_WEIGHT = 1.
3. Reset MD32810 $MA_EQUIV_SPEEDCTRL_TIME.
Setting the equivalent time constant with torque feedforward control
If the previous setting was MD32620 $MA_FFW_MODE = 2:
1. Set MD32620 $MA_FFW_MODE = 4.
2. Set MD32610 $MA_VELO_FFW_WEIGHT = 1.
3. Reset MD32800 $MA_EQUIV_CURRCTRL_TIME.
This also applies when you load an older archive into the control system, e.g. from a
previous version. For example, when changing MD32620 $MA_FFW_MODE from 1 to 3,
MD32810 $MA_EQUIV_SPEEDCTRL_TIME may not simply retain its old value, but must be
reset. Otherwise, no improvement will be achieved, but rather a worsening of the positioning
response.
Recommended setting in case of recommissioning
If recommissioning, or if previous standard values are loaded (switch position 1 on
commissioning switch and POWER ON), the following machine data default values apply:
MD32620 $MA_FFW_MODE = 1
MD32610 $MA_VELO_FFW_WEIGHT = 1
These are not the recommended settings, but are chosen for reasons of compatibility.
However, if recommissioning, the following setting is recommended:
MD32620 $MA_FW_MODE = 3
The balancing time for the speed feedforward control then just has to be adjusted in machine
data:
MD32810 $MA_EQUIV_SPEEDCTRL_TIME.

Table of Contents

Other manuals for Siemens SINUMERIK ONE MCP 2400.4c

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK ONE MCP 2400.4c and is the answer not in the manual?

Siemens SINUMERIK ONE MCP 2400.4c Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK ONE MCP 2400.4c
CategoryControl Systems
LanguageEnglish

Related product manuals