Detailed Description
2.5 Optimization of the control
Velocities, Setpoint/Actual-Value Systems, Closed-Loop Control (G2)
Function Manual, 08/2005 Edition, 6FC5397-0BP10-0BA0
2-67
Setting the equivalent time constant of the current control loop
MD32800 torque feedforward control for each additional option
The same rules and recommendations apply to setting the time constant of the current
control loop as to the speed feedforward control.
However, as previously, activation of the torque feedforward control filter via:
MD32620 $MA_FFW_MODE = 4
must be enabled both in the drive and via the option in order to set the time constant via:
MD32800 $MA_EQUIV_CURRCTRL_TIME.
As with activating the previous filter via:
MD32620 $MA_FFW_MODE = 2,
all other machine data are set in consideration of the corresponding elasticity limits of the
machine.
Limitation to stiff machines
Experience has shown that this expenditure is only worthwhile in the case of very stiff
machines, and requires appropriate experience. The elasticities of the machine are often
excited due to the injection of the torque so strongly that the existing vibrations neutralize the
gain in contour accuracy.
In this case, it would be worth trialing the use of dynamic stiffness control as an alternative:
MD32640 $MA_STIFFNESS_CONTROL_ENABLE.
Example of torque feedforward control
Programming sample of a selection of the torque feedforward control with new balancing and
default setting: FFWON and FFWOF are active.
MD32620 $MA_FFW_MODE[X1] = 4 ; New mode for torque feedforward
control
MD32630 $MA_FFW_ACTIVATION_MODE[X1] = 1 ; FFWON and FFWOF are active.
FFWON now enables the torque feedforward control in the program
(with all axes of the channel with the same settings as X1);
FFWOF will disable them again.
Machine data:
MD20150 $MC_GCODE_RESET_VALUES[23] (G group initial setting)
can be used to set a default value for FFWON for every program.
MD32620 $MA_FFW_MODE[X1] = 4 ; New mode for torque feedforward
control
MD32630 $MA_FFW_ACTIVATION_MODE[X1] = 0 ; FFWON and FFWOF are active.

Table of Contents

Other manuals for Siemens SINUMERIK ONE MCP 2400.4c

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK ONE MCP 2400.4c and is the answer not in the manual?

Siemens SINUMERIK ONE MCP 2400.4c Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK ONE MCP 2400.4c
CategoryControl Systems
LanguageEnglish

Related product manuals