6 - 38
Siemens AG May 1998
Note:
Marshalling of one logical function to 2 or more binary
inputs is not supported (no logical connection). Each
logical function is allocated to one binary input.
Marshalling of several different functions to one biĆ
nary input, however, is allowed.
The general diagrams in annex A.1.2 and table 6.7
show the pre-set binary inputs upon delivery.
Y
B
6 1 0 0 J M A R S H A L L I N G
B I N A R Y I N P U T S
Start of the block "marshalling of binary inputs"
"
A
6 1 0 1 J B I N A R Y
I N P U T 1
Depressing key "ENTER" displays the marshalled
function. Repeated depressing of the "ENTER"-key
starts the change mode.
"
A
1 J I N P U T 1
> I s o l a t o r 1 – o n N O
Binary input 1 is pre-set for isolator status ON for
isolator 1 (refer to table 6.8).
Working-current (A) is selected.
"
A
2 J I N P U T 1
n o t a l l o c a t e d
Input 1 is not allocated to any further functions. Alarm
numbers 2 to 20 are pre-set for "not marshalled",
FNo 001.
The change mode is left by depressing the key
"ESC".
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS52 and is the answer not in the manual?

Siemens SIPROTEC 7SS52 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS52
CategoryProtection Device
LanguageEnglish

Related product manuals