6 - 39
Siemens AG ⋅ May 1998
Table 6.8 Marshallable binary input functions
FNo Short text
(indication on LC-display)
Logical functions
1
5
1156
7000
7001
7002
7003
7004
7005
7006
7007
7008
7009
7020
7021
7022
7023
7024
7025
7026
7027
7028
7029
not marshalled
>LED-ackn
>CB test
>Isol1-Closed
>Isol1-Open
>Isol2-Closed
>Isol2-Open
>Isol3-Closed
>Isol3-Open
>Isol4-Closed
>Isol4-Open
>Isol5-Closed
>Isol5-Open
>CBF L1
>CBF L2
>CBF L3
>CBF pulse
>CBF Rel
>TRIP Rel
>CB Open
>CB CLOSE Com
>CB disturb
>Bay out serv
No function allocated to input
>Reset LED indication
>Start three-pole circuit breaker test
>Isolator status signal Closed for isolator 1
>Isolator status signal Open for isolator 1
>Isolator status signal Closed for isolator 2
>Isolator status signal Open for isolator 2
>Isolator status signal Closed for isolator 3
>Isolator status signal Open for isolator 3
>Isolator status signal Closed for isolator 4
>Isolator status signal Open for isolator 4
>Isolator status signal Closed for isolator 5
>Isolator status signal Open for isolator 5
>Circuit breaker failure initiation for phase L1
>Circuit breaker failure initiation for phase L2
>Circuit breaker failure initiation for phase L3
>Circuit breaker failure initiation via pulse
>Circuit breaker failure release signal
>Trip command release
>Bus coupler circuit breaker in OPEN status
>CLOSE command for bus coupler circuit breaker
>Circuit breaker disturbed
>Control bay out of service
Table 6.9 Pre-set binary inputs
Direct
address
1st display line 2nd display line FNo Note
6100
6101
6102
6103
6104
6105
6106
6107
6108
6109
6110
6111
6112
6113
6114
6115
6116
6117
6118
6119
6120
MARSHALLING
BINARY INPUT 1
BINARY INPUT 2
BINARY INPUT 3
BINARY INPUT 4
BINARY INPUT 5
BINARY INPUT 6
BINARY INPUT 7
BINARY INPUT 8
BINARY INPUT 9
BINARY INPUT 10
BINARY INPUT 11
BINARY INPUT 12
BINARY INPUT 13
BINARY INPUT 14
BINARY INPUT 15
BINARY INPUT 16
BINARY INPUT 17
BINARY INPUT 18
BINARY INPUT 19
BINARY INPUT 20
>BINARY INPUTS
>Isol1-Closed
>Isol1-Open
>Isol2-Closed
>Isol2-Open
>Isol3-Closed
>Isol3-Open
>Isol4-Closed
>Isol4-Open
>Isol5-Closed
>Isol5-Open
>CBF L1
>CBF L2
>CBF L3
>CB-CLOSE com
>CBF rel
>CB test
>CB Open
not marshalled
>CB disturb
>Bay out serv
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
7000
7001
7002
7003
7004
7005
7006
7007
7008
7009
7020
7021
7022
356
7024
1156
7026
1
7028
7029
Isolator status signal Closed for isolator 1
Isolator status signal Open for isolator 1
Isolator status signal Closed for isolator 2
Isolator status signal Open for isolator 2
Isolator status signal Closed for isolator 3
Isolator status signal Open for isolator 3
Isolator status signal Closed for isolator 4
Isolator status signal Open for isolator 4
Isolator status signal Closed for isolator 5
Isolator status signal Open for isolator 5
Circuit breaker failure initiation for phase L1
Circuit breaker failure initiation for phase L2
Circuit breaker failure initiation for phase L3
Close command for bus coupler circuit breaker
Circuit breaker failure protection release signal
start three-pole circuit breaker test
Bus coupler circuit breaker in Open status
No function is allocated to input
Circuit breaker failure disturbed
Control bay out of service
A: working-contact
R: quiescent-contact