System data
5000 CHANGE SYST./DESIGN DATA?
5100 SYST:DATA.: System state ?
5101 REBOOT =blocked (blocked, released)
5102 LED COL ISO =red for CLOSED (green f. CLOSED, red f. CLOSED)
5103 FAULT RESPO =released (blocked, released)
5104 AUT LED ACK =blocked (blocked, released)
5105 FRECUENCY =50 Hz (50 Hz, 60 Hz)
5106 I>SUM SUPV =.50 I/IN *) (min. 0.20 – max. 1.00)
5107 OFFSET SUPV =.10 V (min. 0.10 – max. .50)
5108 15 V SUPV =1.50 V (min. 0.50 – max. 2.50)
5200 SYST:DATA: Serial link ?
5201 TERMBAUD CU =19200 Baud (min. 1.200 – max. 38400)
5400 DESGN DATA: Common configur?
5401 PROT TR BUS =blocked (blocked, released)
5402 BAY DC FAIL =OLD isol status (OLD isol status, isol CLOSED)
5403 ISOL ST 1/1 =OLD isol status (OLD isol status, isol CLOSED)
5404 BB–ISOLAT 4 =BB–isolator (TR–isolator, BB–isolator)
_______________
 IN – Nominal current of the bay current
transformer