Configuring
6.2 Configuring the 3RW5 Soft Starter
SIRIUS 3RW5 Modbus TCP communication module
Manual, 03/2018, A5E43676481002A/RS-AA/001
43
1. Set the required IP parameters in the 3RW5 soft starter.
The following procedures are possible:
Via SIRIUS Soft Starter ES (TIA Portal) over the LAN interface on the 3RW5 HMI High
Feature
Via the 3RW5 HMI High Feature
Menu: "Parameter > Communication > Modbus TCP > IP address"
Menu: "Parameter > Communication > Modbus TCP > Subnet mask"
Menu: "Parameter > Communication > Modbus TCP > Address of router"
You will find more information on operating the 3RW5 HMI High Feature in the Manual
of the 3RW5 soft starter.
Note the information in chapter IP parameters (Page 44).
2. Start the Modbus client in your automation system and address the server (3RW5 soft
starter) using the previously set IP parameter.
When using a SIMATIC S7-1500, for example, integrate the FB "MB_CLIENT" into the
user program.
Note the information in chapter IP parameters (Page 44).
3. Load the configuration into the client (if necessary).
Result
The 3RW5 soft starter is configured in the Modbus TCP system and can communicate with
other Modbus TCP devices via the 3RW5 Modbus TCP communication module.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS 3RW5 series and is the answer not in the manual?

Siemens SIRIUS 3RW5 series Specifications

General IconGeneral
BrandSiemens
ModelSIRIUS 3RW5 series
CategoryController
LanguageEnglish

Related product manuals