A.2.13
Process image output (PIQ)
Read (r) and write (w) access to the process image output (PIQ) is possible.
Read access via Function Codes 01, 02, 03, and 04
Write access via function codes 05, 06, 15, and 16
Read and write access combined via function code 23
Register
Byte
Bit address
Data format
Process image
3RW
Address
high / low
52
1)
55
2)
0x8200 high
0x8200
Bool
Motor CW
r/w
r/w
0x8201
Bool
Motor CCW
-
r/w
0x8203
Bool
Reset
r/w
r/w
0x8204
Bool
Emergency start
-
r/w
0x8205 Bool Self-test (user-test) r/w r/w
0x8206
Bool
Creep speed
-
r/w
low
0x8208
Bool
Output 1
-
r/w
0x8209
Bool
Output 2
-
r/w
0x820A
Bool
Parameter set bit 0*
-
r/w
0x820B
Bool
Parameter set bit 1*
-
r/w
0x820F
Bool
Disable Quick-stop
-
r/w
0x8201 high
0x8210
Bool
Output 3
-
r/w
0x8213
Bool
Pump cleaning mode
-
r/w
low
0x8218
Bool
Manual operation local - input controlled
r/w
r/w
0x8219
Bool
Use alternative stopping mode
-
r/w
0x821A
Bool
Motor standstill
-
r/w
1)
Supported by SIRIUS 3RW52 soft starter
2)
Supported by SIRIUS 3RW55 soft starter
* Explanation in the following table
More information
The following table describes the assignment of the process images "Parameter set bit 0"
and "Parameter set bit 1":
Process image
Process image error
Parameter set 1 (PS1)
Parameter set 2 (PS2)
Parameter set 3 (PS3)
Parameter set bit 0
1
0
1
0
Parameter set bit 1
1
0
0
1