EasyManua.ls Logo

Siemens SIRIUS 3RW5 series - I&M1 - Basic Unit; I&M2 - Basic Unit; I&M3 - Basic Unit

Siemens SIRIUS 3RW5 series
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.2 Data tables
SIRIUS 3RW5 Modbus TCP communication module
78 Manual, 03/2018, A5E43676481002A/RS-AA/001
A.2.7
I&M1 - Basic unit
For access to the function tag and location tag (I&M1) read access (r) is possible via
Function Codes 03 and 04. Write access (w) is possible via function codes 06 and 16.
Register
Content
Access
Address
Quantity
0x01A1
5
RESERVED
r
0x01A6
16
TAG_FUNCTION
r/w
0x01B6
11
TAG_LOCATION
r/w
A.2.8
I&M2 - Basic unit
For access to the installation date (I&M2) read access (r) is possible via Function Codes 03
and 04. Write access (w) is possible via function codes 06 and 16.
Register
Content
Access
Address
Quantity
0x01C1
5
RESERVED
r
0x01C6
8
INSTALLATION_DATE
r/w
0x01CE
19
RESERVED
r
A.2.9
I&M3 - Basic unit
For access to the description (I&M3) read access (r) is possible via Function Codes 03
and 04. Write access (w) is possible via function codes 06 and 16.
Register
Content
Access
Address
Quantity
0x01E1
5
RESERVED
r
0x01E6
27
DESCRIPTOR
r/w

Table of Contents