Messages and diagnostics
7.2 Function Codes
SIRIUS 3RW5 Modbus TCP communication module
Manual, 03/2018, A5E43676481002A/RS-AA/001
59
Function Code 23 (Read/Write Multiple Registers)
This function enables the Modbus client system to write and read several registers from
3RW5 register memory area using a single function call.
Note
Read/Write Multiple Registers
With the FC
23, it is only possible to access the process image output (PIQ) and the process
The write operation is the first executed operation here. This function is the typically used
function call for outputting cyclic data in the 3RW5 soft starter and for reading back inputs or
device statuses.
A valid address from the bit memory area is expected as the start address. The selected
address must be designated as writable in the data tables in chapter Data tables (Page 75).
Start address read
operation
Number of registers
(read access)
Start address write
operation
Number of registers N
(write access)
Number of bytes
(write access)