EasyManua.ls Logo

Siemens SIRIUS 3RW5 series - I&M0 - Communication; I&M0 - Basic Unit; A.2.5 I&M0 - Communication

Siemens SIRIUS 3RW5 series
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.2 Data tables
SIRIUS 3RW5 Modbus TCP communication module
Manual, 03/2018, A5E43676481002A/RS-AA/001
77
A.2.5
I&M0 - Communication
For the device overview (I&M0) only read access (r) is possible via Function Codes 03
and 04.
Register
Content
Access
Address
Quantity
0x00C1
5
RESERVED
r
0x00C6
1
MANUFACTURER_ID
r
0x00C7
10
ORDER_ID
r
0x00D1
8
SERIAL_NUMBER
r
0x00D9 1 HARDWARE_REVISION r
0x00DA
2
SOFTWARE_REVISION
r
0x00DC
1
REV_COUNTER
r
0x00DD
1
PROFILE_ID
r
0x00DE
1
PROFILE_SPECIFIC_TYPE
r
0x00DF
1
IM_VERSION
r
0x00E0
1
IM_SUPPORTED
r
A.2.6
I&M0 - Basic unit
For the device overview (I&M0) only read access (r) is possible via Function Codes 03
and 04.
Register
Content
Access
Address
Quantity
0x0181
5
RESERVED
r
0x0186
1
MANUFACTURER_ID
r
0x0187
10
ORDER_ID
r
0x0191
8
SERIAL_NUMBER
r
0x0199
1
HARDWARE_REVISION
r
0x019A
2
SOFTWARE_REVISION
r
0x019C
1
REV_COUNTER
r
0x019D
1
PROFILE_ID
r
0x019E
1
PROFILE_SPECIFIC_TYPE
r
0x019F 1 IM_VERSION r
0x01A0
1
IM_SUPPORTED
r