Appendix
A.2 Data tables
SIRIUS 3RW5 Modbus TCP communication module
82 Manual, 03/2018, A5E43676481002A/RS-AA/001
A.2.14
Soft starter diagnostics
For access to the soft starter diagnostics only read access (r) is possible via Function Codes
01, 02, 03 and 04.
Register
Byte
Bit address
Data format
Soft starter diagnostics
3RW
Address
high / low
52
1)
55
2)
0x8400 high
0x8400
Bool
Ready (automatic)
r
r
0x8401
Bool
Motor CW
r
r
0x8402
Bool
Motor CCW
-
r
0x8403
Bool
Switching element overload
r
r
0x8404 Bool Switching element defective r r
0x8405
Bool
Emergency start active
-
r
0x8406
Bool
Group error
r
r
0x8407
Bool
Group warning
r
r
low
0x8409
Bool
No main power
r
r
0x840B
Bool
Start mode active
r
r
0x840C
Bool
Stop mode active
r
r
0x840E
Bool
Electrical braking active
-
r
0x840F
Bool
Creep speed active
-
r
0x8401 high
0x8410
Bool
Temperature sensor overload
r
r
0x8411
Bool
Temperature sensor wire break
r
r
0x8412
Bool
Temperature sensor short-circuit
r
r
0x8413
Bool
Thermal motor model overload
r
r
0x8414
Bool
Motor overload shutoff
r
r
0x8415
Bool
Idle time active
-
r
0x8416
Bool
Cooling time active
r
r
low
0x841B
Bool
Current limiting active
r
r
0x841E
Bool
Generator operation
-
r
0x841F
Bool
Input control
-
r
0x8402 high 0x8420 Bool Asymmetry limit - error exceeded - r
0x8421
Bool
Asymmetry shutoff
-
r
0x8422
Bool
Current limit error exceeded
-
r
0x8423
Bool
Current limit error undershot
-
r
0x8424
Bool
Current error limit shutoff
-
r
low
0x8428
Bool
Input 1
r
r
0x8429
Bool
Input 2
-
r
0x842A
Bool
Input 3
-
r
0x842B
Bool
Input 4
-
r
0x8403 high
0x8430
Bool
Ground fault limit error exceeded
-
r
0x8432
Bool
Quick stop active
-
r
0x8436
Bool
Maximum pointer reset
-
r
0x8437 Bool Electronics supply voltage too low r r