3RT1/3RH1 contactors
SIRIUS System Manual
GWA 4NEB 430 0999-02b
3-125
3RT13 contactors, 4-pole (4 NO contacts), for switching resistive loads
Contactor Frame size
Type
S00
3RT13 16
S00
3RT13 17
S0
3RT13 25
S0
3RT13 26
S2
3RT13 36
S3
3RT13 44
S3
3RT13 46
Main circuit
Current carrying capacity with alternating current
Utilization category AC-1, switching of resistive loads
Rated operational currents
I
e
(at 40 °C)
(at 60 °C)
Up to
690 V
Up to
690 V
A
A
18
16
22
20
35
30
40
35
60
55
110
100
140
120
Rated power of three-phase loads
cos
ϕ
= 0.95 (at 40 °C)
At 230 V
400 V
kW
kW
7
12
8.5
14.5
12.5
22
15
26
23
39
42
72
53
92
Minimum conductor cross-section loaded with
I
e
At 40 °C
and 60 °C
mm
2
2.5 2.5 10 10 16 50 50
Utilization categories AC-2 and AC-3
Rated operational currents
I
e
(at 60 °C) At 400 V A 9 12 17 25 26
Rated power of slipring or squirrel-cage motors at
50 Hz and 60 Hz
At 230 V
400 V
kW
kW
3
4
3
5.5
4
7. 5
5.5
11
5.5
11
Contactor Frame size
Type
S00
3RT13 16
S00
3RT13 17
S0
3RT13 25/26
Current carrying capacity with direct current
Utilization category DC-1, switching of resistive loads (L/R
≤
1 ms)
Rated operational currents
I
e
(at 40 °C)
Number of conducting paths in series connection
1234 1234 1234
up to 24 V
60 V
110 V
220 V
440 V
A
A
A
A
A
18 18 18 18
18 18 18 18
2.1 12 18 18
0.8 1.6 18 18
0.6 0.8 1.3 1.3
22 22 22 22
22 22 22 22
2.1 12 22 22
0.8 1.6 22 22
0.6 0.8 1.3 1.3
35 35 35 35
20 35 35 35
4.5353535
1 5 35 35
0.4 1 2.9 2.9
Utilization categories DC-3 and DC-5
shunt and series motors (L/R
≤
15 ms)
Rated operational currents
I
e
(at 40 °C)
Number of conducting paths in series connection
1234 1234 1234
Up to 24 V
60 V
110 V
220 V
440 V
A
A
A
A
A
18 18 18 18
0.5 5 18 18
0.15 0.35 18 18
---- ---- 1.5 1.5
---- ---- 0.2 0.2
20 20 20 20
0.5 5 20 20
0.15 0.35 20 20
---- ---- 1.5 1.5
---- ---- 0.2 0.2
20 35 35 35
5353535
2.5 15 35 35
131035
0.09 0.27 0.6 0.6
Contactor Frame size
Type
S2
3RT13 36
S3
3RT13 44
S3
3RT13 46
Current carrying capacity with direct current
Utilization category DC-1, switching of resistive loads (L/R
≤
1 ms)
Rated operational currents
I
e
(at 40 °C)
Number of conducting paths in series connection
1234 1234 1234
Up to 24 V
60 V
110 V
220 V
440 V
A
A
A
A
A
50 50 50 50
23 45 45 45
4.5 45 45 45
1 5 45 45
0.4 1 2.9 2.9
70 70 70 70
23 70 70 70
4.5707070
1 5 70 70
0.4 1 2.9 2.9
80 80 80 80
60 80 80 80
9808080
2108080
0.6 1.8 4.5 4.5
Utilization categories DC-3 and DC-5
shunt and series motors (L/R
≤
15 ms)
Rated operational currents
I
e
(at 40 °C)
Number of conducting paths in series connection
1234 1234 1234
Up to 24 V
60 V
110 V
220 V
440 V
A
A
A
A
A
20 45 45 45
6454545
2.5 25 45 45
1 5 25 45
0.1 0.27 0.6 0.6
20 70 70 70
6707070
2.5707070
1 7 35 70
0.15 0.42 0.8 0.8
20 80 80 80
6.5808080
2.5808080
1 7 35 80
0.15 0.42 0.8 0.8