Communication
11.10 DR 7 Process interfaces
SIWAREX WT241
132 Manual, 05/2015, A5E36046748A
Value
Response
0
Trace recording runs as circulating memory
1
Trace is stopped when the trace memory is full
11.10.14 Load per pulse
By parameterizing the corresponding digital output you can use one of the digital outputs as
a pulse sensor/quantity (see Assignment digital output DQ 0, 1, 2, 3 (Page 128)).
In addition you must specify a load per pulse and a pulse duration for the signal. If the
material flow rate is displayed e.g. in t/h, you must specify the quantity per pulse in t, or with
kg/h in kg. The pulse duration is defined in ms.
Make sure when setting the parameters that you only enter plausible combinations → pulse
duration > (amount per pulse / material flow rate)