EasyManua.ls Logo

Siemens SIWAREX WT241 - Electrical, EMC and Climatic Requirements

Siemens SIWAREX WT241
185 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
12.2 Electrical, EMC and climatic requirements
SIWAREX WT241
176 Manual, 05/2015, A5E36046748A
12.2 Electrical, EMC and climatic requirements
Electrical protection and safety requirements
Table 12- 11 Requirements: Electrical protection and safety requirements
Met requirement
Standards
Comments
Safety regulations
IEC 61010-1
Protection class
IEC 61140
IP degree of protection
IP 65 nach IEC 60529
Air gaps and creepage
distances
IEC 61010-1
Overvoltage category II
Pollution degree 2
PCB material IIIa
Conductor path distance 0.5 mm
Isolation stability
IEC 61131-2
CSA C22.2, No. 142
UL508
IEC 61010-1
Mains Enclosure:
AC 1500V
Mains SELV circuits:
AC 3000V
Electromagnetic compatibility
Table 12- 12 Requirements: Interference emission in industrial area in accordance with EN 61000-6-4
Comments
Standard
Limits
Emission of radio interferences
(electromagnetic fields)
Class B residential environment:
EN 55011+A1:2010
Cispr 11+A1:2010
30 ... 230 MHz, 40 dB
(μV/m) QP
230 ... 1 000 MHz, 47 dB
(μV/m) QP
Emission on power supply
Class B: residential environ-
ment:
EN 55011+A1:2010
Cispr 11+A1:2010
Class A: Industrial environment
0,15 ... 0,5 MHz,
66 56dB(uV) Q*
56 46dB(uV) A*
0,5 ... 30 MHz,
56dB(uV) Q
46dB(uV) A
0,5 ... 30 MHz,
60 dB(uV) Q
50 dB(uV) A

Table of Contents