9.3 Message list
SIWAREX WT241
84 Manual, 05/2015, A5E36046748A
Technology error (code 2000 to 4999)
Error code
Description and remedy
3001 Totalizer error
3001
Fault occurred during totalizing.
3002 Calibration procedure interrupted
3002
Current calibration procedure has been aborted. Possible causes:
non-plausible values have been determined during the command.
9.3.3 Data and operating errors message list
Data and operating errors
(code 5000 to 8999)
Error code
Description and remedy
5000 Data and operating error exists
5000
Group error, a bit is set in the data and operating error bits
5001 Command code or data record un-
known
5001
Command code or data record is not known with current
application
5002 Command or data change not possi-
ble because write protection is active
5002
The command or changing of data is not possible due to write
protection. The data record was rejected.
5003 Cannot exit service mode
5003
Cannot exit calibration mode; calibration incomplete
5004 Command or data transmission only
available in service mode
5004
Activation of service mode is required to execute command or
transmit data
5006 Command or data transmission not
possible because of BUSY
5006
Command can currently not be executed because module is
BUSY (data record or command transmission already active,
…)
5007 Command or data transmission not
possible because module is faulty or
SIMATIC CPU stop
5007
Command can currently not be executed because of a prob-
lem or SIMATIC CPU stop
5104 Command not possible because
range is exceeded
5104
Command (e.g. set to zero, tare, calibrate command) cannot
be executed because the permitted range has been exceed-
ed. The ranges are defined in DR 3.
5105 Load cell parameters not plausible
5105
Load cell parameters in data record DR 10 are not plausible
(number, support points, load specifications, etc.).
5108 ID does not exist
5108
Requested logbook ID not present in memory.
5199 Error in command to DI
5199
Processing of a command triggered at the DIs is not possible.
The cause can be determined in data record DR 32.
6002 Logging not possible because weight
is too small
6002
Logging is not possible because the limits for the minimum
weight or maximum weight were not observed.
6003 Command cannot be executed since
a dynamic procedure is already active
6003
Desired command cannot be executed since a dynamic
command (calibration, zeroing) is already being executed.
6004 Command cannot be executed since
a dynamic procedure is not active
6004
Desired command cannot be executed since a dynamic
command is not currently being executed.
7000 Permitted number range violated
7000
The permitted number range, such as for weight values, was
violated.
7001 Regulation code not known
7001
Regulation code for application requiring official calibration
not known.
7002 Specifications of string lengths not
plausible
7002
The string header in a specified string variable is not plausi-
ble.
7003 Specification of date / time not plau-
sible
7003
Specifications for date and time are not plausible.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIWAREX WT241 and is the answer not in the manual?

Siemens SIWAREX WT241 Specifications

General IconGeneral
BrandSiemens
ModelSIWAREX WT241
CategoryAccessories
LanguageEnglish

Related product manuals