Connecting 
  6.6 Connection of digital inputs (4 x DI) 
SIWAREX WT241 
Manual, 05/2015, A5E36046748A  37 
6.6  Connection of digital inputs (4 x DI) 
Unknown assignment of digital inputs 
If the assignment of the digital inputs is not known at the time of connection, this may 
damage parts of the system. 
Do not create a connection with the digital inputs before you know the assignment. 
The electronic weighing system described here has four digital inputs. They can be found 
directly at the weighing module SIWAREX WP241 and are not connected through to the 
terminal board. 
The digital inputs are not permanently assigned to commands in the delivery state. 
Assignment of the digital inputs to commands is carried out during commissioning by 
parameter assignment in menu 1.5.1 “Digital in- and outputs”. 
The external 24 V switching signal is connected electrically isolated to the desired input, the 
associated ground to terminal 2M. 
When using a speed sensor it is essential to connect it to digital input DI.0. In addition, the 
input must be defined as a speed sensor input in menu 1.5.1.1 “Digital in- and output 
settings 1 of 2”  
Table 6- 4  Connection of the digital inputs 
Digital input 0 (input for speed sensor) 
Reference ground potential of the digital inputs