EasyManuals Logo

Siemens XC10 Series User Manual

Siemens XC10 Series
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
Standards
11
Building Technologies A6V10257473_b_en_--.doc
Fire Safety & Security Products 01.2010
3 Standards
In addition to the requirements of EN12094-1 and EN54-2, the XC10xx-A control
panel complies with the following optional functions:
EN 12094-1
Clause Description
4.17 Delay of extinguishing signal
4.18 Signal representing the flow of extinguishing agent
4.19 Monitoring the status of components
4.20 Emergency hold device
4.21 Control of flooding time
4.23 Manual only mode
4.24 Triggering signals to equipment within the system
4.26 Triggering of equipment outside the system
4.27 Emergency abort device
4.29 Release of the extinguishing media for selected flooding zones (only for XC1003-A)
4.30 Activation of alarm device with different signals
EN 54-2 / A1
Clause Description
7.8 Output to fire alarm devices (Item C – EN54-1)
7.9.1 Control of fire alarm routing equipment (Item E – EN54-1)
7.12.1 Dependencies on more than one alarm signal (Type A)
7.13 Alarm counter (only with XC1005-A)
8.3 Fault signals from point
8.4 Total loss of the power supply
8.9 Output to fault warning routing equipment (Item J – EN54-1)
10 Test condition
Following additional functions are also available:
- transmission of information's outside the panel:
8 programmable digital outputs
programmable relay contacts
- reception of information's from outside:
control inputs (3 are programmable)
- 24V power supply output

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens XC10 Series and is the answer not in the manual?

Siemens XC10 Series Specifications

General IconGeneral
BrandSiemens
ModelXC10 Series
CategoryControl Unit
LanguageEnglish

Related product manuals