EasyManuals Logo

Siemens XC10 Series User Manual

Siemens XC10 Series
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #60 background imageLoading...
Page #60 background image
Programming
60
Building Technologies A6V10257473_b_en_--.doc
Fire Safety & Security Products 01.2010
Same options as non monitored control input 2 – default = 12
1)
State is maintained as long as a potential +24V is applied
2)
Pulse control (0.2 s minimum)
3)
Control must be possible through a level 2 access device only
12.14 Steps 52 to 55 - Detection zones
Step
Option
Description
Alarm verification: select zones (*)
01 No alarm verification
02 Zone 1
03 Zone 2
04 Zones 1 and 2
05 Zone 3
06 All zones
52
(*)The alarm condition is enabled only after 2 consecutive alarms in less than 60 seconds (the 1st one is reset automatically). The
delay for the second alarm is 8 s. If the second alarm doesn’t come within 60 s, the first alarm is automatically reseted. The first
alarm is indicated by the red led during 2 s.
Automatic release: select zones combination
01 Alarm zone 1 AND Alarm zone 2
02 ( Alarm zone 1 AND Alarm zone 2 ) OR ( Fault zone 1 AND Alarm zone 2 ) OR ( Alarm zone 1 AND Fault zone 2 )
03 Alarm zone 1 AND Alarm zone 2 AND Alarm zone 3
04 ( Alarm zone 1 AND Alarm zone 2) OR Alarm zone 3
05 ( Alarm zone 1 AND Alarm zone 3 ) OR ( Alarm zone 2 AND Alarm zone 3 ) OR ( Alarm zone 1 AND Alarm zone 2 )
06 Alarm zone 1 OR Alarm zone 2
53
07 Alarm zone 1
Care shall be taken using option 04, 06 and 07 as it triggers the extinguishing process on a single alarm
Zones disabling
01 Zone "Disable" and zone "Test" is allowed
54
02 Zone "Disable" and zone "Test" is not possible
Application: installations where it is not permitted to suppress automatic detection ( CO
2
for example)
Zone 3 : Fire alarm condition
01 "Fire alarm" condition indicated, RT-Alarm activated
55
02 "Fire alarm" condition indicated, RT-Alarm not activated
12.15 Steps 56 to 57 – Operating access level
Step
Option
Description
"Silence buzzer": change access level
01 Possible at access levels 1 and 2
56
02 Possible at access level 2 only
Access level 2
01 Default code = 4 2 3 3
02 Individual access code:
1. Enter the desired code on the keyboard (4 to 6 digits)
2. Press the key (12) "Disable / Test zone 1" :
red led zone 1 (25) flashes
3. Repeat operations 1 and 2 (code confirmation) :
red led zone 1 (25) lights continuously = code accepted
yellow led zone 1 (26) flashes = code not accepted (repeat operations 1 to 3)
57
03 Operating access level 2 is provided with an external optional key (in this case, code access is not possible)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens XC10 Series and is the answer not in the manual?

Siemens XC10 Series Specifications

General IconGeneral
BrandSiemens
ModelXC10 Series
CategoryControl Unit
LanguageEnglish

Related product manuals