7.6.1 Monitored control output 1
This output is exclusively reserved for the connection of the Sounders. Operation is
defined at programming step 05 (see paragraph 12.4).
3.3 kΩ
Fig. 21 XC10xx-A, monitored control output 1 connection
7.6.2 Monitored control output 2
This output can be used for several purposes. Operation is defined at programming
step 11 (see paragraph 12.6).
3.3 kΩ
Fig. 22 XC10xx-A, monitored control output 2 connection
1 RT-alarm
2 Fire control(s): signal triggering to equipment outside the system, according to
EN12094-1 option with requirements 4.26
3 Sounder(s)
4 Warning panel(s) « Mechanical blocked » or « Automatic or manual blocked »
or « Automatic and manual blocked »
7.6.3 Monitored control output 3
This output is exclusively reserved for the connection of the warning panels.
Operation is defined at programming step 12 (see paragraph 12.6).
3.3 kΩ
Fig. 23 XC10xx-A, monitored control output 3 connection