Connections
37
Building Technologies A6V10257473_b_en_--.doc
Fire Safety & Security Products 01.2010
7.6.5 Monitored control output 5
This output can be used for several purposes. Operation is defined at programming
steps 03 and 14 (see paragraphs 12.3 and 12.6).
Fig. 25 XC10xx-A, monitored control output 5 connection
1 Actuators (electromagnetic or pyrotechnic)
2 Fire control(s): signal triggering to equipment outside the system according to
EN12094-1 option with requirements 4.26
3 Warning panel(s) « Mechanical blocked » or « Automatic or manual blocked »
or « Automatic and manual blocked »
4 Output not used
If this output is used to connect actuators, characteristics of the monitored output 4 (line length,
programming options, etc.) apply.