Multi-sector installation
45
Building Technologies A6V10257473_b_en_--.doc
Fire Safety & Security Products 01.2010
8.4 Multi-sector modules technical specification
XCA1031:
Actuator output 1 and 2:
- device can be either electromagnetic or pyrotechnic actuator
- activation by reverse polarity (polarities indicated are “activated” polarities,
according to connected device, a diode can be necessary)
- line monitoring: 3.3 k resistance connected at the end of the line
- protection: 1 AF fuse (F1 / F2)
- cable type: 2 x 2.5mm
2
max.
- length / resistance of the line: see paragraph 7.6
Loss of agent input:
- line monitoring: 3.3 k resistance connected at the end of the line
- line resistance: 80 max.
XCA1030:
Selector valve position monitoring input:
- line monitoring: 3.3 k resistance connected at the end of the line
- line resistance: 80 max.