3-4
3. Use the PC Programmer’s List Tab to add the initiating devices and output
points to the appropriate lists, as follows:
List Add These Points
L9 Automatic Suppression Release Points. Add all automatic
initiating devices whose activation should result in the release
of the suppression agent.
L10
Suppression Manual Release Points. Add all manual
suppression release points whose activation should result in
the release of the suppression agent.
L12
Suppression Release Output Points. Add the NACs that
control the suppression release solenoids.
Default Suppression Release Applications, Continued
Programming Default
Applications (continued)