A-9
Visual – on until silence. Points assigned with this point type are ON when any
point within L1, General Alarm List, goes into alarm. Visual Notification
Appliances assigned this point type remain ON until an Alarm Silence is
performed.
Circuit Status LCD Display
System Status
Normal Visual ON
Normal Visual OFF
Visual CODING
Disable TBL Visual TROUBLE
OFF AUTO TBL Visual TROUBLE
Waterflow signal – on until silence. Points with this point type turn ON when
any point in L2, Waterflow Alarm Monitor List, goes into alarm. Points remain
activated until the Alarm Silence.
Circuit Status LCD Display
System Status
ON Signal Circuit ON
OFF Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
Disable TBL Signal Circuit TROUBLE
Trouble/Supervisory Signal On until Clear. Points with this point type turn ON
when any trouble or supervisory condition occurs. Points turn OFF when the
trouble or supervisory condition is cleared.
Circuit Status LCD Display
System Status
ON Signal Circuit ON
ON Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
Disable TBL Signal Circuit TROUBLE
Continued on next page
Point Types, Continued
SVISUAL
SWATER
TSIGNAL